2905012 – QUINT-PS/96-110DC/24DC/10/CO – BỘ NGUỒN QUINT CÓ PHỦ LỚP BẢO VỆ 10A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
DC operation
Nominal input voltage range 96 V DC … 110 V DC
Input voltage range 67.2 V DC … 154 V DC
Wide-range input yes
Input voltage range DC 67.2 V DC … 154 V DC
Voltage type of supply voltage DC
Inrush current < 10 A (typical)
Inrush current integral (I2t) 0.37 A2s
Mains buffering time typ. 10 ms (96 V DC)
Current consumption 3.5 A (96 V DC)
3.1 A (110 V DC)
Reverse polarity protection ≤ 154 V DC
Protective circuit Transient surge protection; Varistor
Input fuse 10 A 150 V DC (internal (device protection))
Efficiency > 92 % (UIN 96 V DC / UOUT 24 V DC)
> 92 % (UIN 110 V DC / UOUT 24 V DC)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-40 °C … 60 °C)
POWER BOOST (IBoost) 12.5 A (-40°C … 40°C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation 18 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 240 W
Peak switching voltages nominal load < 10 mVPP (20 MHz)
Maximum no-load power dissipation 4 W (UIN 110 V DC)
Power loss nominal load max. 22 W (UIN 110 V DC)
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes