2910128 – QUINT4-PS/48DC/48DC/5/PT – BỘ NGUỒN QUINT4 5A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
Nominal input voltage range 48 V DC
Input voltage range 48 V DC -40 % … +20 %
Wide-range input no
Electric strength, max. 60 V DC (60 s)
Inrush current typ. 2.3 A
Inrush current integral (I2t) < 0.1 A2s
Inrush current limitation 2.3 A
Mains buffering time typ. 17 ms (48 V DC)
Current consumption 6.8 A (48 V DC)
Typical response time 300 ms (from SLEEP MODE)
Switch-on time < 1 s
Input fuse 20 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Efficiency typ. 95.2 % (48 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 48 V DC
Setting range of the output voltage (USet) 48 V DC ... 56 V DC (> 48 V constant capacity)
Nominal output current (IN) 5 A
Static Boost (IStat.Boost) 6.25 A
Dynamic Boost (IDyn.Boost) 10 A (5 s)
Selective Fuse Breaking (ISFB) 30 A (15 ms)
Magnetic circuit breaker tripping A1 … A6 / B2 / C1 … C2 / Z1 … Z6
Short-circuit-proof yes
No-load proof yes
Output power (PN) 240 W
Output power (PStat. Boost) 300 W
Output power (PDyn. Boost) 480 W (5 s)
Feedback voltage resistance ≤ 60 V DC
Protection against overvoltage at the output (OVP) ≤ 60 V DC
Residual ripple < 50 mVPP
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Rise time < 100 ms (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 3 W
Power loss nominal load max. < 13 W
Power dissipation SLEEP MODE < 2 W
Connection in parallel yes, for redundancy and increased capacity