2910122 – QUINT4-PS/24DC/12DC/8/PT – BỘ NGUỒN DC 8A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
Nominal input voltage range 24 V DC
Input voltage range 24 V DC -25 % … +40 %
Wide-range input no
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 3 A
Inrush current integral (I2t) < 0.02 A2s
Inrush current limitation 1 A
Mains buffering time typ. 17 ms (24 V DC)
Current consumption 5.5 A (24 V DC)
Typical response time 300 ms (from SLEEP MODE)
Switch-on time < 1 s
Input fuse 15 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Efficiency typ. 91 % (24 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 12 V DC
Setting range of the output voltage (USet) 12 V DC ... 15 V DC (> 12 V DC, constant capacity)
Nominal output current (IN) 8 A
Static Boost (IStat.Boost) 10 A
Dynamic Boost (IDyn.Boost) 16 A (5 s)
Selective Fuse Breaking (ISFB) 48 A (15 ms)
Magnetic circuit breaker tripping A1 … A6 / B2 … B6 / Z1 … Z6
Short-circuit-proof yes
No-load proof yes
Output power (PN) 96 W
Output power (PStat. Boost) 120 W
Output power (PDyn. Boost) 192 W (5 s)
Feedback voltage resistance ≤ 25 V DC
Protection against overvoltage at the output (OVP) ≤ 18 V DC
Residual ripple < 13 mVPP
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Rise time < 100 ms (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 2 W
Power loss nominal load max. < 9 W
Power dissipation SLEEP MODE < 1 W
Connection in parallel yes, for redundancy and increased capacity