AC operation
Network type Star network
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Switch-on voltage > 75 V AC
Shut-down voltage < 70 V AC
Electric strength, max. 300 V AC 15 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 20 A
Inrush current integral (I2t) < 0.5 A2s
Inrush current limitation typ. 20 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz ±5 Hz
Frequency range (fN) 50 Hz ... 60 Hz ±10 %
Mains buffering time typ. 20 ms (120 V AC)
typ. 20 ms (230 V AC)
Current consumption 3.1 A (100 V AC)
2.4 A (120 V AC)
1.3 A (230 V AC)
1.4 A (240 V AC)
Nominal power consumption 285 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.93
Typical response time < 1 s
Input fuse 6.3 A (internal (device protection))
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
0.8 mA (264 V AC, 60 Hz)
POWER factor > 0.9 (120 V AC)
> 0.8 (230 V AC)
DC operation
Nominal input voltage range 110 V DC … 250 V DC
Input voltage range 110 V DC … 250 V DC -10 % … +10 %
Extended input voltage range in operation 88 V DC … 99 V DC (Derating <99 V DC: 2.5 %/V)
Derating < 99 V DC (2 %/V)
Switch-on voltage ≥ 95 V DC
Shut-down voltage < 70 V DC
Voltage type of supply voltage AC/DC
Mains buffering time > 15 ms (230 V AC)
Current consumption 2.5 A (110 V DC)
1.1 A (250 V DC)
Efficiency typ. 90 % (120 V AC)
typ. 91.5 % (230 V AC)
Output characteristic U/I with dynamic load reserve
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC … 28 V DC (constant capacity)
Nominal output current (IN) 10 A
Dynamic Boost (IDyn.Boost) 15 A (5 s)
Derating > 60 °C … 70 °C (2.5%/K)
POWER factor > 0.9 (120 V AC)
> 0.8 (230 V AC)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 240 W
360 W
Maximum no-load power dissipation < 5.1 W
Power loss nominal load max. < 25 W
Rise time ≤ 50 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal relay 13/14
Default closed
Digital 30 V AC 30 V DC 100 mA