1066708 – QUINT4-PS/48-110DC/24DC/2.5/PT – BỘ NGUỒN QUINT4 2.5 A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
Nominal input voltage range 48 V DC … 110 V DC
Input voltage range 48 V DC … 110 V DC -37,5 % …+40 %
Wide-range input yes
Electric strength, max. 160 V DC (60 s)
Inrush current typ. 8 A
Inrush current integral (I2t) typ. 0.1 A2s
Inrush current limitation 8 A
Mains buffering time typ. 14 ms (48 V DC)
typ. 17 ms (110 V DC)
Current consumption typ. 1.7 A (48 V DC)
typ. 0.75 A (110 V DC)
Switch-on time < 1 s
Input fuse 4 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Efficiency typ. 93.7 % (110 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 2.5 A
Static Boost (IStat.Boost) 3.125 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 5 A (≤ 60 °C (4,9 s))
Short-circuit-proof yes
No-load proof yes
Derating > 60 °C (2.5%/K of POut nom.)
Output power (PN) 60 W
Output power (PStat. Boost) 75 W
Output power (PDyn. Boost) 120 W
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Residual ripple < 20 mVPP
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Rise time < 1 s (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 2.2 W
Power loss nominal load max. < 4.8 W
Connection in parallel yes, for redundancy and increased capacity