1168602 – QUINT4-PS/3AC/24DC/20/VASS – BỘ NGUỒN QUINT4 3 PHA 20A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
AC operation
Network type Star network
Nominal input voltage range 3x 400 V AC … 500 V AC
2x 400 V AC … 500 V AC
Input voltage range 3x 400 V AC … 500 V AC -20 % … +10 %
2x 400 V AC … 500 V AC -10 % … +10 %
Typical national grid voltage 400 V AC
480 V AC
Voltage type of supply voltage AC
Inrush current typ. 2 A (at 25 °C)
Inrush current integral (I2t) < 0.1 A2s
Inrush current limitation 3 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time typ. 33 ms (3x 400 V AC)
typ. 33 ms (3x 480 V AC)
Current consumption 3x 0.99 A (400 V AC)
3x 0.81 A (480 V AC)
2x 1.62 A (400 V AC)
2x 1.37 A (480 V AC)
3x 0.8 A (500 V AC)
2x 1.23 A (500 V AC)
Nominal power consumption 541 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.94
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Recommended breaker for input protection 3x 4 A ... 20 A (Characteristic B, C or comparable)
Recommended fuse for input protection ≥ 300 V AC
Discharge current to PE < 3.5 mA
1.7 mA (550 V AC, 60 Hz)
DC operation
Nominal input voltage range ± 260 V DC ... 300 V DC
Input voltage range ± 260 V DC ... 300 V DC -13 % ... +30 %
Voltage type of supply voltage DC
Current consumption 1.23 A (± 260 V DC)
1.06 A (±300 V DC)
Recommended breaker for input protection 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection ≥ 1000 V DC
Efficiency typ. 93.9 % (400 V AC)
typ. 93.8 % (480 V AC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 26 V DC
Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN) 20 A
Static Boost (IStat.Boost) 25 A
Dynamic Boost (IDyn.Boost) 30 A (5 s)
Selective Fuse Breaking (ISFB) 120 A (15 ms)
Magnetic circuit breaker tripping A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating > 60 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 60 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 480 W
600 W
720 W
Apparent power 686 VA (400 V, UOUT = 24 V, IOUT = stat. Boost)
698 VA (480 V, UOUT = 24 V, IOUT = stat. Boost)
Maximum no-load power dissipation < 7 W (400 V AC)
< 7 W (480 V AC)
Power loss nominal load max. < 32 W (400 V AC)
< 33 W (480 V AC)
Power dissipation SLEEP MODE < 5 W (400 V AC)
< 5 W (480 V AC)
Crest factor typ. 1.78 (400 V AC)
typ. 2.1 (480 V AC)
Rise time < 80 ms (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes