2903148 – TRIO-PS-2G/1AC/24DC/5 – BỘ NGUỒN TRIO 1 PHA 5A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
- Hình ảnh thực tế
AC operation
Network type Star network
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Input voltage range AC 85 V AC … 264 V AC
Electric strength, max. ≤ 300 V AC 15 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current ≤ 16 A (typical)
Inrush current integral (I2t) < 0.6 A2s
Inrush current limitation typ. 16 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz ±10 %
Mains buffering time typ. 20 ms (120 V AC)
typ. 100 ms (230 V AC)
Current consumption 2.2 A (100 V AC)
1.9 A (120 V AC)
1.1 A (230 V AC)
1.1 A (240 V AC)
Nominal power consumption 272 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.5
Typical response time < 1 s
Input fuse 6.3 A (internal (device protection))
Recommended breaker for input protection 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE < 0.25 mA
DC operation
Nominal input voltage range 110 V DC ... 250 V DC
Input voltage range 99 V DC ... 275 V DC
Switch-on voltage ≥ 88 V DC
Shut-down voltage < 60 V DC
Voltage type of supply voltage AC/DC
Mains buffering time > 100 ms (230 V AC)
Current consumption 1.4 A (110 V DC)
0.6 A (250 V DC)
Efficiency > 90 % (for 230 V AC and nominal values)
Output characteristic U/I with dynamic load reserve
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 24 V DC … 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A
Dynamic Boost (IDyn.Boost) 7.5 A (5 s)
Derating > 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Output power 120 W
180 W
Maximum no-load power dissipation < 1 W
Power loss nominal load max. < 16 W
Rise time ≤ 12 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK
Maximum switching voltage 30 V AC/DC
Continuous load current 100 mA