2904611 – QUINT4-PS/1AC/48DC/10 – BỘ NGUỒN QUINT4 1 PHA 10A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
AC operation
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Derating < 100 V AC (1 %/V)
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current typ. 11 A (at 25 °C)
Inrush current integral (I2t) < 0.4 A2s
Inrush current limitation 11 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time typ. 32 ms (120 V AC)
typ. 32 ms (230 V AC)
Current consumption 6.8 A (100 V AC)
5.5 A (120 V AC)
2.8 A (230 V AC)
2.7 A (240 V AC)
Nominal power consumption 519 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Input fuse 12 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE < 3.5 mA
1.3 mA (264 V AC, 60 Hz)
Efficiency typ. 94 % (120 V AC)
typ. 95 % (230 V AC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 48 V DC
Setting range of the output voltage (USet) 48 V DC ... 56 V DC (constant capacity)
Nominal output current (IN) 10 A
Static Boost (IStat.Boost) 12.5 A
Dynamic Boost (IDyn.Boost) 15 A (5 s)
Selective Fuse Breaking (ISFB) 60 A (15 ms)
Magnetic circuit breaker tripping A1...A13 / B2...B6 / C1...C3 / Z1...Z10
Derating > 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 60 V DC
Protection against overvoltage at the output (OVP) ≤ 60 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 70 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 480 W
600 W
720 W
Apparent power 660 VA (120 V, UOUT = 48 V, IOUT = stat. Boost)
644 VA (230 V, UOUT = 48 V, IOUT = stat. Boost)
Maximum no-load power dissipation < 5 W (120 V AC)
< 5 W (230 V AC)
Power loss nominal load max. < 36 W (120 V AC)
< 28 W (230 V AC)
Power dissipation SLEEP MODE < 5 W (120 V AC)
< 5 W (230 V AC)
Crest factor typ. 1.54 (120 V AC)
typ. 1.56 (230 V AC)
Rise time < 1 s (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes