2902646 – TRIO-PS/1AC/5DC/10 – BỘ NGUỒN TRIO 1PHA 10A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
- Hình ảnh thực tế
Nominal input voltage range | 100 V AC … 240 V AC |
Input voltage range | 85 V AC … 264 V AC (Derating < 90 V AC: 2.5 %/K) |
Derating | < 90 V AC (2.5 %/V) |
Input voltage range AC | 85 V AC … 264 V AC (Derating < 90 V AC: 2.5 %/K) |
Electric strength, max. | 300 V AC |
Voltage type of supply voltage | AC |
Inrush current | < 30 A |
Inrush current integral (I2t) | < 1.9 A2s |
AC frequency range | 45 Hz … 65 Hz |
Mains buffering time | > 40 ms (120 V AC) |
> 180 ms (230 V AC) | |
Current consumption | 1 A (120 V AC) |
0.5 A (230 V AC) | |
Nominal power consumption | 131.4 VA |
Protective circuit | Transient surge protection; Varistor |
Power factor (cos phi) | 0.48 |
Typical response time | < 1 s |
Permissible backup fuse | B6 B10 B16 |
Recommended breaker for input protection | 6 A … 16 A (Characteristics B, C, D, K) |
Discharge current to PE | < 3.5 mA |
Efficiency | > 80 % (230 V AC) |
Output characteristic | U/I |
Nominal output voltage | 5 V DC ±1 % |
Setting range of the output voltage (USet) | 4.5 V DC … 6 V DC (> 12 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A (-25 °C … 55 °C) |
Derating | 55 °C … 70 °C (2.5%/K) |
Feedback voltage resistance | approx. 9 V DC |
Protection against overvoltage at the output (OVP) | < 9 V DC |
Max. capacitive load | unlimited |
Active current limitation | Approx. 12 A (in the event of a short-circuit) |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (change in load, dynamic 10 % … 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 60 mVPP |
Output power | 50 W |
Peak switching voltages nominal load | < 70 mVPP |
Maximum no-load power dissipation | 1.5 W |
Power loss nominal load max. | 13.5 W |
Rise time | < 2 ms (UOUT (10 % … 90 %)) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Bạn đang cần tư vấn?