BỘ NGUỒN QUINT-PS/1AC/24DC/ 5 – 2866750 PHOENIX CONTACT
- Thông tin kỹ thuật
- Tải catalog
- Hình ảnh thực tế
AC operation
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC
110 V DC … 350 V DC (typ. 90 V DC (UL 508: ≤ 300 V DC))
Electric strength, max. 300 V AC
Voltage type of supply voltage AC/DC
Inrush current < 15 A
Inrush current integral (I2t) < 1 A2s AC frequency range 45 Hz … 65 Hz Frequency range DC 0 Hz Mains buffering time > 55 ms (120 V AC)
> 55 ms (230 V AC)
Current consumption 1.2 A (120 V AC)
0.6 A (230 V AC)
1.3 A (110 V DC)
0.6 A (220 V DC)
Nominal power consumption 145 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.94
Typical response time < 0.15 s
Input fuse 5 A (slow-blow, internal)
Permissible backup fuse B6 B10 B16 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 6 A … 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA Efficiency > 90 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A (-25 °C … 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost) 7.5 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 30 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / C2
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (with nominal values)
Output power 120 W
Maximum no-load power dissipation 3 W
Power loss nominal load max. 15 W
Rise time < 0.1 s (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes