2320144 – QUINT-PS/48DC/24DC/ 5 – BỘ NGUỒN QUINT 5A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
DC operation
Nominal input voltage range 48 V DC
Input voltage range 30 V DC … 60 V DC
Wide-range input no
Input voltage range DC 30 V DC … 60 V DC
Voltage type of supply voltage DC
Inrush current < 5 A (typical)
Inrush current integral (I2t) < 0.2 A2s
Mains buffering time > 14 ms (48 V DC)
Current consumption 3.5 A (48 V DC)
Protective circuit Transient surge protection; Varistor
Input fuse 10 A (slow-blow, internal)
Permissible backup fuse B10 B16
Recommended breaker for input protection 10 A … 16 A (Characteristics B, C, D, K)
Efficiency > 91.5 %
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A (-25 °C … 60 °C)
POWER BOOST (IBoost) 6.25 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 30 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / C2
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation Approximately 6.9 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 25 mVPP
Output power 120 W
Peak switching voltages nominal load < 5 mVPP (20 MHz)
Maximum no-load power dissipation 2.7 W
Power loss nominal load max. 11 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes