AC operation
Supply system configuration Star network (TN, TT, IT (PE))
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC ±10 %
Switch-on voltage > 75 V AC
Shut-down voltage < 70 V AC
Electric strength, max. ≤ 300 V AC 15 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current ≤ 25 A (typical)
Inrush current integral (I2t) < 0.5 A2s
Inrush current limitation typ. 25 A (after 1 ms)
Frequency range (fN) 50 Hz ... 60 Hz ±10 %
Mains buffering time > 15 ms (120 V AC)
> 15 ms (230 V AC)
Current consumption 2.2 A (100 V AC)
0.9 A (240 V AC)
Nominal power consumption 285 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) > 0.93
Switch-on time < 1 s
Input fuse 6.3 A (internal (device protection))
Recommended breaker for input protection 6 A ... 16 A (US/CAN: branch circuit protection < 20 A) (Characteristic B, C, D, K or comparable)
Discharge current to PE < 3.5 mA
DC operation
Nominal input voltage range 110 V DC ... 250 V DC
Input voltage range 110 V DC ... 250 V DC ±10 %
Switch-on voltage ≥ 95 V DC
Shut-down voltage < 95 V DC
Voltage type of supply voltage AC/DC
Mains buffering time > 15 ms (230 V AC)
Current consumption 1.9 A (110 V DC)
0.8 A (250 V DC)
Efficiency typ. 91 % (120 V AC)
typ. 93 % (230 V AC)
Nominal output voltage 24 V DC ±1 %
Nominal output current (IN) 8 A
Dynamic Boost (IDyn.Boost) 12 A (5 s)
Derating > 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 30 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple ≤ 10 mVPP
Short-circuit-proof yes
No-load proof yes
Output power 192 W
288 W
Maximum no-load power dissipation < 8 W (120 V AC)
< 5 W (230 V AC)
Power loss nominal load max. < 18 W (120 V AC)
< 14 W (230 V AC)
Rise time ≤ 12 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal: DC OK
Maximum switching voltage 30 V AC/DC
Continuous load current 100 mA
Signal relay 13/14
Default closed
Digital 30 V AC 30 V DC 100 mA