2904605 – QUINT4-PS/1AC/12DC/2.5/PT – BỘ NGUỒN QUINT4 1 PHA 2.5A – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
AC operation
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 11.3 A (at 25 °C)
Inrush current integral (I2t) < 0.1 A2s
Inrush current limitation < 11.3 A
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time typ. 54 ms (120 V AC)
typ. 54 ms (230 V AC)
Current consumption 0.44 A (100 V AC)
0.35 A (120 V AC)
0.19 A (230 V AC)
0.2 A (240 V AC)
Nominal power consumption 32.8 VA
Protective circuit Transient surge protection; Varistor
Typical response time 500 ms
Input fuse 3.15 A (slow-blow, internal)
Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE < 0.25 mA (264 V AC, 60 Hz)
< 0.16 mA
DC operation
Input voltage range 110 V DC ... 250 V DC -20 % ... +40 %
Voltage type of supply voltage AC/DC
Current consumption 0.4 A (110 V DC)
0.17 A (250 V DC)
Efficiency typ. 89.5 % (120 V AC)
typ. 90.9 % (230 V AC)
Nominal output voltage 12 V DC
Setting range of the output voltage (USet) 12 V DC ... 15 V DC (constant capacity)
Nominal output current (IN) 2.5 A
Static Boost (IStat.Boost) 3.125 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 4.5 A (≤ 60 °C (5 s))
Feedback voltage resistance ≤ 25 V DC
Protection against overvoltage at the output (OVP) ≤ 18 V DC
Control deviation < 0.2 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 30 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 30 W
38 W
54 W
Maximum no-load power dissipation < 0.4 W (230 V AC)
< 0.5 W (120 V AC)
Power loss nominal load max. < 3.5 W (120 V AC)
< 3 W (230 V AC)
Crest factor typ. 1,89 (120 V AC)
typ. 1,97 (230 V AC)
Rise time 50 ms (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes