2320186 – QUINT-ORING/24DC/2X20/1X40 – BỘ NGUỒN QUINT-ORING – PHOENIX CONTACT – TIENHUNGTECH
- Thông tin kỹ thuật
- Tải catalog
- Hình ảnh thực tế
DC operation
Nominal input voltage range 24 V DC
Input voltage range 18 V DC … 28 V DC (SELV)
Input voltage range DC 18 V DC … 28 V DC (SELV)
Voltage type of supply voltage DC
Reverse polarity protection < yes60 V
Nominal input current (IN) 2x 20 A (-25 °C ... 60 °C)
1x 40 A (-25 °C ... 60 °C)
Maximum current Imax 2x 26 A (-25°C ... 40°C)
1x 52 A (-25°C ... 40°C)
120 A (12 ms, SFB Technology)
Transient surge protection Varistor
Voltage drop, input/output 0.2 V (IOUT = 40 A)
Efficiency > 98 %
Nominal output voltage 0.2 V (< DC input)
Output voltage UIn -
Nominal output current (IN) 40 A (Increasing power)
20 A (Redundancy)
Derating 60 °C ... 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP) < 32 V DC
Power loss nominal load max. 8 W (IOUT = 40 A)
Connection in series No
Signal: Redundancy OK, 13/14
Output description Group contact
Maximum switching voltage max. 30 V AC/DC
Maximum inrush current ≤ 100 mA (short-circuit-proof)
Signal: ACB (Auto Current Balancing) OK, 23/24
Output description Contact closed: Δ UIN ≤ 300 mV
Maximum switching voltage max. 30 V AC/DC
Maximum inrush current ≤ 100 mA (short-circuit-proof)