DC operation
Nominal input voltage range 24 V DC
Input voltage range 18 V DC … 32 V DC
Extended input voltage range in operation 14 V DC … 18 V DC (Derating)
Wide-range input no
Input voltage range DC 18 V DC … 32 V DC
14 V DC … 18 V DC (Consider derating during operation)
Voltage type of supply voltage DC
Inrush current < 26 A (typical)
Inrush current integral (I2t) < 11 A2s
Mains buffering time typ. 10 ms (24 V DC)
Current consumption 28 A (24 V, IBOOST)
Reverse polarity protection ≤ yes30 V DC
Protective circuit Transient surge protection; Varistor
Recommended breaker for input protection 40 A ... 50 A (Characteristics B, C, D, K)
Efficiency > 93 %
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 20 A (-25 °C … 60 °C)
POWER BOOST (IBoost) 25 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 120 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6
Derating 60 °C … 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation approx. 29 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 480 W
Peak switching voltages nominal load < 10 mVPP (20 MHz)
Maximum no-load power dissipation 2.2 W
Power loss nominal load max. 39 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes