SAFETY RELAY PHOENIX PSR-M-E2-DO16-SC – 1105134
- Technical information
- Download catalog
Maximum power dissipation for nominal condition | 3.5 W (with max. permissible load) |
Nominal operating mode | 100% operating factor |
Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
Air clearances and creepage distances between the power circuits | |
Rated insulation voltage | 250 V AC |
Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
Supply | |
Designation | A1/A2 |
Rated control circuit supply voltage US | 19.2 V DC … 28.8 V DC |
Rated control circuit supply voltage US | 24 V DC -20 % / +20 % (provide external protection, typically 5 A) |
Rated control supply current IS | typ. 30 mA |
Power consumption at US | typ. 0.72 W |
Inrush current | 2 A (Δt = 1 ms at Us) |
Filter time | typ. 5 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal |
Suppressor diode | |
Supply | |
Designation | 24V/A2 |
Rated control circuit supply voltage US | 24 V DC -20 % / +20 % (provide external protection, typically 5 A) |
Rated control supply current IS | typ. 20 mA (Outputs active, without load) |
Inrush current | 10 A (at both terminal points 5 and 6, Δt = 1 ms at Us) |
Filter time | typ. 1 ms (in the event of voltage dips) |
Protective circuit | Suppressor diode |
Are you in need of advice?