MST 1-PHASE CONTROL AND ISOLATION TRANSFORMER, 1× 230, 1× 115, 2× 115 V AC/1000 VA – 86151
- Technical information
- Download catalog
GENERAL DATA
Standards | EN 61558-1, EN 61558-2-4, EN 62041 category 0 |
---|---|
Mounting method | Key-hole mounting |
Temperature range | -20…+40 °C (storage temperature -40…+80 °C) |
Test isolation voltage | 4 kV (prim./sec.) |
Drill hole Ø | 7×11 mm |
Fixing centers a×b×c | 102×135×7 mm |
Dimensions H×W×D | 128×174×160 mm |
OUTPUT
Output voltage | 1× 230, 1× 115, 2× 115 V AC |
---|---|
Output rating | 1000 VA |
INPUT
Input voltage | 208, 230, 380, 400, 420, 440, 460, 480, 500, 525, 550 V AC |
---|---|
Inrush current | 66 A (230 V AC); 38 A (400 V AC) |
Short-circuit current | 148 A (230 V AC); 85 A (400 V AC) |
Input current | 4.73 A (230 V AC); 2.72 A (400 V AC) |
Frequency | 50…60 Hz |
Are you in need of advice?