POWER SUPPLY MURRELEKTRONIK ECO-RAIL-2 1 PHASE, 24 V DC/2.5 A – 85132
- Technical information
- Download catalog
Standards | IEC 61010-2-201, EN 61204-3, EN 61000-3-2 |
---|---|
Mounting method | DIN-rail mountable TH35 (EN 60715) |
Temperature range | 0…+40 °C, …+55 °C derating (storage temperature -20…+85 °C) |
Relative humidity | 20…90%, no condensation |
Protection | IP20 |
Efficiency | 84% (115 V AC); 85% (230 V AC) |
Connection | Screw terminals |
Dimensions H×W×D | 125×50×84 mm |
OUTPUT
Output voltage | 24 V DC ±1%; 23…28 V adjustable |
---|---|
LED display | LED (green) for output voltage |
Output current | 2.5 A (+40 °C); 2.0 A (+55 °C) |
Mains failure bridging time | min. 20 ms (115 V AC); min. 100 ms (230 V AC) |
Ripple | max. 10 mV eff/rms |
Spikes | max. 50 mV ss/pp |
Unit protection | short-circuit and overload protected |
Parallel usage/serial usage | no/yes (max. 2 units) |
INPUT
Input voltage | 100…240 V AC |
---|---|
Input current | 1.3 A (100 V AC); 0.6 A (240 V AC) |
Inrush current after 1 ms | max. 20 A (230 V AC) |
Frequency | 50…60 Hz |
Input fuse (internal) | 4 A (T) |
Product article number of manufacturer | 85132 |
---|