2904595 – QUINT4-PS/1AC/5DC/5/PT – BỘ NGUỒN QUINT4 1 PHA 5A – PHOENIX CONTACT – TIENHUNGTECH
- Technical information
- Download catalog
AC operation
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Electric strength, max. 300 V AC (60 s)
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 9.1 A (at 25 °C)
Inrush current integral (I2t) < 0.1 A2s
Inrush current limitation < 9.1 A
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time typ. 52 ms (120 V AC)
typ. 52 ms (230 V AC)
Current consumption 0.37 A (100 V AC)
0.3 A (120 V AC)
0.17 A (230 V AC)
0.16 A (240 V AC)
Nominal power consumption 32.8 VA
Protective circuit Transient surge protection; Varistor
Typical response time 350 ms
Input fuse 3.15 A (slow-blow, internal)
Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE < 0.25 mA (264 V AC, 60 Hz)
typ. 0.08 mA
Efficiency typ. 87.4 % (120 V AC)
typ. 88.4 % (230 V AC)
Nominal output voltage 5 V DC
Setting range of the output voltage (USet) 5 V DC ... 6.2 V DC (constant capacity)
Nominal output current (IN) 5 A
Static Boost (IStat.Boost) 6.25 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 8 A (≤ 60 °C (5 s))
Feedback voltage resistance ≤ 16 V DC (16 V e-caps in output circuit)
Protection against overvoltage at the output (OVP) < 8 V DC
Control deviation < 0.3 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10% ... 90%, 10 Hz < 4%)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 25 W
31 W
40 W
Maximum no-load power dissipation < 0.37 W (120 V AC)
< 0.41 W (230 V AC)
Power loss nominal load max. < 3.7 W (120 V AC)
< 3.3 W (230 V AC)
Crest factor typ. 1.88 (120 V AC)
typ. 2.09 (230 V AC)
Rise time 50 ms (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes