2909575 – QUINT4-PS/1AC/24DC/1.3/PT – BỘ NGUỒN QUINT 1PHA 1.3 A – PHOENIX CONTACT – TIENHUNGTECH
- Technical information
- Download catalog
- Photo realistic
AC operation
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Electric strength, max. 300 V AC 30 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC/DC
Inrush current typ. 5.9 A (at 25 °C)
Inrush current integral (I2t) < 0.1 A2s
Inrush current limitation 5.9 A
< 14 A
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time typ. 43 ms (120 V AC)
typ. 43 ms (230 V AC)
Current consumption 0.46 A (100 V AC)
0.37 A (120 V AC)
0.2 A (230 V AC)
0.2 A (240 V AC)
Nominal power consumption 37 VA
Protective circuit Transient surge protection; Varistor
Typical response time 500 ms
Input fuse 3.15 A (slow-blow, internal)
Discharge current to PE < 0.25 mA (264 V AC, 60 Hz)
0.18 mA (264 V AC, 60 Hz)
Efficiency typ. 89.2 % (120 V AC)
typ. 90.7 % (230 V AC)
Output characteristic U/I Advanced
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN) 1.3 A
Static Boost (IStat.Boost) 1.625 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 2.6 A (≤ 60 °C (5 s))
Derating > 60 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 40 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 30 W
38 W
60 W
Maximum no-load power dissipation < 0.4 W (230 V AC)
< 0.4 W (120 V AC)
Power loss nominal load max. < 3.7 W (120 V AC)
< 3.1 W (230 V AC)
Crest factor typ. 1.71 (120 V AC)
typ. 1.94 (230 V AC)
Rise time 50 ms (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal (configurable)