2866404 – TRIO-PS/3AC/24DC/40 – 40A 3-PHA TRIO POWER SUPPLY – PHOENIX CONTACT – TIENHUNGTECH
- Technical information
- Download catalog
- Photo realistic
AC operation
Nominal input voltage range 3x 400 V AC … 500 V AC
Input voltage range 3x 320 V AC … 575 V AC
2x 360 V AC … 575 V AC (for 2-phase operation)
Input voltage range AC 3x 320 V AC … 575 V AC
2x 360 V AC … 575 V AC (for 2-phase operation)
Voltage type of supply voltage AC
Inrush current < 20 A Inrush current integral (I2t) 1.3 A2s AC frequency range 45 Hz … 65 Hz Mains buffering time > 16 ms (400 V AC)
> 20 ms (480 V AC)
Current consumption 3x 2 A (400 V AC)
3x 1.6 A (480 V AC)
Nominal power consumption 1387 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.76
Typical response time < 1 s
Permissible backup fuse B10 B16
Recommended breaker for input protection 6 A … 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA Efficiency > 91.5 % (at 400 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 40 A (-25 °C … 55 °C)
Derating 55 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation Approx. 48 A
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 960 W
Peak switching voltages nominal load < 40 mVPP
Maximum no-load power dissipation 16 W
Power loss nominal load max. 91 W
Rise time < 2 ms (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes