SAFETY RELAY PHOENIX PSR-MC82-5NO-1NC-1DO-24DC-SC – 2702382
- Technical information
- Download catalog
Maximum power dissipation for nominal condition | 15.2 W (at US = 30 V, IL² = 64 A²) |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits | |
Rated insulation voltage | 250 V AC |
250 V AC | |
Rated surge voltage/insulation | |
Supply | |
Designation | A1/A2 |
Rated control circuit supply voltage US | 19.2 V DC … 30 V DC |
Rated control circuit supply voltage US | 24 V DC -20 % / +25 % |
Rated control supply current IS | typ. 80 mA |
Power consumption at US | typ. 1.92 W |
Inrush current | typ. 125 mA (Δt = 7 ms at Us) |
Filter time | 4 ms (at A1 in the event of voltage dips at Us) |
max. 1 ms (at A1/A2, test pulse width, blanking pulses/dark test) | |
5 ms (at A1/A2, test pulse rate, blanking pulses/dark test) | |
Where test pulse width < 1 ms: test pulse rate = 5 x test pulse width | |
max. 1 ms (at A1/A2, test pulse width, switch-on pulses/light test) | |
10 ms (at A1/A2; test pulse rate; switch-on pulses/light test) | |
Deactivate the switch-on pulses for safety applications. | |
Protective circuit | Surge protection; Suppressor diode |
Reverse polarity protection; Universal diode |