SAFETY RELAY PHOENIX PSR-MC62-2NO-1DO-24DC-SC – 2700574
- Technical information
- Download catalog
Maximum power dissipation for nominal condition | 5.09 W (at US = 30 V, IL² = 72 A²) |
Nominal operating mode | 100% operating factor |
Air clearances and creepage distances between the power circuits | |
Rated insulation voltage | 250 V AC |
250 V AC | |
Rated surge voltage/insulation | Basic insulation 4 kV between all current paths and housing |
Safe isolation, reinforced insulation 6 kV: between (A1, A2, S11, S12, S21, S22, S35, M1) and enabling current path (13/14) between (A1, A2, S11, S12, S21, S22, S35, M1) and enabling current path (23/24) between enabling current paths |
|
Supply | |
Designation | A1/A2 |
Rated control circuit supply voltage US | 19.2 V DC … 30 V DC |
Rated control circuit supply voltage US | 24 V DC -20 % / +25 % |
Rated control supply current IS | typ. 40 mA |
Power consumption at US | typ. 0.96 W |
Inrush current | typ. 20 A (Δt = 10 µs at Us) |
Filter time | 10 ms (For the logic. At A1 in the event of voltage dips at Us ) |
Protective circuit | Surge protection; Suppressor diode |
Protection against polarity reversal for rated control circuit supply voltage |
Are you in need of advice?