SAFETY RELAY PHOENIX PSR-M-EF3-SDI12-MAT-SC – 1104885
- Technical information
- Download catalog
Maximum power dissipation for nominal condition | 4.28 W (with max. permissible load) |
Nominal operating mode | 100% operating factor |
Interfaces | DIN rail TBUS for connection to the master module, supplied as standard |
Air clearances and creepage distances between the power circuits | |
Rated insulation voltage | 250 V AC |
Rated surge voltage/insulation | Basic insulation 4 kV between 24 V power supply and I/Os to the housing |
Supply | |
Designation | A1/A2 |
Rated control circuit supply voltage US | 19.2 V DC … 28.8 V DC |
Rated control circuit supply voltage US | 24 V DC -20 % / +20 % (external fuse, typically 4 A) |
Rated control supply current IS | typ. 53 mA |
Power consumption at US | typ. 1.27 W |
Inrush current | < 2 A (Δt = 1.5 ms at Us) |
Filter time | typ. 10 ms (at A1 in the event of voltage dips at Us) |
Protective circuit | Serial protection against polarity reversal |