RELAY MODULE KFD0-RSH-1-Y2 – PEPPERL+FUCHS
- Technical information
- Download catalog
1-channel signal conditioner < 24 V DC supply (loop powered) < Logic input 20 V DC … 30 V DC, non-polarized < Fail-safe relay contact output < Test pulse immunity < Up to SIL 3 acc. to IEC/EN 61508 Input Connection side control side Connection terminals 7, 8 Pulse/Pause ratio min. 35 ms / min. 35 ms Pulse/Pause ratio test pulse < 10 % Test pulse length max. 2 ms Signal level 0-signal: 0 … 5 V DC 1-signal: 20 … 30 V Rated current approx. 58 mA Output Connection side field side Connection terminals 2, 3 Contact loading 230 V AC/2 A/cos φ 0.7; 40 V DC/2 A resistive load Minimum switch current 2 mA / 24 V DC Energized/De-energized delay 5 … 15 ms / 5 … 10 ms Mechanical life 5 x 106 switching cycles Electrical life 2 x 105 switching cycles , at maximum load Fuse rating 2.5 A recommended maximum utilization of the fuse: 80 %