MTL 1-PHASE CONTROL AND ISOLATION TRANSFORMER, 1× 24/1× 48/2× 24 V AC/250 VA – 86455
- Technical information
- Download catalog
Standards | EN 61558-2-4, EN 61558-2-6, EN 62041 category 0 |
---|---|
Mounting method | DIN-rail mountable TH35-15 (EN 60715) or for key-hole mounting |
Temperature range | -20…+60 °C, no condensation |
Test isolation voltage | 5.1 kV (prim./sec.) |
Drill hole Ø | 5.5×9 mm |
Fixing centers a×b×c | 96×60×5.5 mm |
Dimensions H×W×D | 153×123×142 mm |
OUTPUT
Output voltage | 1× 24/1× 48/2× 24 V AC |
---|---|
Output rating | 250 VA |
INPUT
Input voltage | 230/400 ±15 V AC |
---|---|
Inrush current | 5.4 A (230 V AC); 3.12 A (400 V AC) |
Short-circuit current | 10 A (230 V AC); 5.77 A (400 V AC) |
Input current | 0.52 A (230 V AC); 0.3 A (400 V AC) |
Frequency | 50…60 Hz |
Product article number of manufacturer | 86455 |
---|