2910121 – QUINT4-PS/24DC/24DC/20/PT – BỘ NGUỒN QUINT 20A – PHOENIX CONTACT – TIENHUNGTECH
- Technical information
- Download catalog
Nominal input voltage range 24 V DC -25 % … +40 %
Input voltage range 24 V DC -25 % … +40 %
Wide-range input no
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 2.7 A
Inrush current integral (I2t) < 0.2 A2s
Inrush current limitation 2.7 A (after 1 ms)
Mains buffering time typ. 16 ms (24 V DC)
Current consumption 27 A (24 V DC)
Typical response time 300 ms (from SLEEP MODE)
Switch-on time < 1 s
Recommended breaker for input protection 50 A (Characteristic B, C or comparable)
Efficiency typ. 94.7 % (24 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 20 A
Static Boost (IStat.Boost) 25 A
Dynamic Boost (IDyn.Boost) 30 A (5 s)
Selective Fuse Breaking (ISFB) 120 A (15 ms)
Magnetic circuit breaker tripping A1…A16 / B2…B13 / C1…C6 / Z1…Z16
Short-circuit-proof yes
No-load proof yes
Output power (PN) 480 W
Output power (PStat. Boost) 600 W
Output power (PDyn. Boost) 720 W (5 s)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Residual ripple < 50 mVPP
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Control deviation < 3 % (change in load, static 10 % ... 90 %)
Rise time < 100 ms (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 4 W
Power loss nominal load max. < 26.6 W
Power dissipation SLEEP MODE < 2 W
Connection in parallel yes, for redundancy and increased capacity