2910120 – QUINT4-PS/24DC/24DC/10/PT – BỘ NGUỒN QUINT4 10A – PHOENIX CONTACT – TIENHUNGTECH
- Technical information
- Download catalog
Nominal input voltage range 24 V DC
Input voltage range 24 V DC -25 % … +40 %
Wide-range input no
Electric strength, max. 35 V DC (60 s)
Inrush current typ. 1.5 A
Inrush current integral (I2t) < 0.02 A2s
Inrush current limitation 1.5 A (after 1 ms)
Mains buffering time typ. 11 ms (24 V DC)
Current consumption 13.8 A (24 V DC)
Typical response time 300 ms (from SLEEP MODE)
Switch-on time < 1 s
Input fuse 30 A (slow-blow, internal)
Recommended breaker for input protection 16 A ... 20 A (Characteristic B, C, D, K or comparable)
Efficiency typ. 93.3 % (24 V DC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 10 A
Static Boost (IStat.Boost) 12.5 A
Dynamic Boost (IDyn.Boost) 20 A (5 s)
Selective Fuse Breaking (ISFB) 60 A (15 ms)
Magnetic circuit breaker tripping A1…A6 / B2…B6 / C1…C3 / Z1…Z6
Short-circuit-proof yes
No-load proof yes
Output power (PN) 240 W
Output power (PStat. Boost) 300 W
Output power (PDyn. Boost) 480 W (5 s)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Residual ripple < 50 mVPP
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Control deviation < 1 % (change in load, static 10 % ... 90 %)
Rise time < 100 ms (UOUT (10 % ... 90 %))
Connection in series yes
Maximum no-load power dissipation < 5 W
Power loss nominal load max. < 16 W
Power dissipation SLEEP MODE < 2 W
Connection in parallel yes, for redundancy and increased capacity