2904623 – QUINT4-PS/3AC/24DC/40 – QUINT4 3-PHASE 40A POWER SUPPLY – PHOENIX CONTACT – TIENHUNGTECH
- Technical information
- Download catalog
Control input (configurable) Rem Output power ON/OFF (SLEEP MODE)
Default Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Network type Star network
Nominal input voltage range 3x 400 V AC … 500 V AC
2x 400 V AC … 500 V AC
Input voltage range 3x 400 V AC … 500 V AC -20 % … +10 %
2x 400 V AC … 500 V AC -10 % … +10 %
Typical national grid voltage 400 V AC
480 V AC
Voltage type of supply voltage AC/DC
Inrush current type. 1.5 A (at 25 °C)
Inrush current integral (I2t) < 0.06 A2s
Inrush current limitation 1.5 A (after 1 ms)
AC frequency range 50 Hz … 60 Hz -10 % … +10 %
Frequency range (fN) 50 Hz … 60 Hz -10 % … +10 %
Mains buffering time type. 28 ms (3x 400 V AC)
type. 28 ms (3x 480 V AC)
Current consumption 3x 1.8 A (400 V AC)
3x 1.5 A (480 V AC)
2x 3 A (400 V AC)
2x 2.5 A (480 V AC)
3x 1.5 A (500 V AC)
2x 2.4 A (500 V AC)
Nominal power consumption 1217 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.95
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Recommended breaker for input protection 3x 4 A … 20 A (Characteristic B, C, D, K or comparable)
Recommended fuse for input protection 300 V AC
Discharge current to PE < 3.5 mA 1 mA (550 V AC, 60 Hz) Efficiency type. 95.7 % (400 V AC) type. 95.7 % (480 V AC) Nominal output voltage 24 V DC Setting range of the output voltage (USet) 24 V DC … 29.5 V DC (constant capacity) Nominal output current (IN) 40 A Static Boost (IStat.Boost) 45 A Dynamic Boost (IDyn.Boost) 60 A (5 s) Selective Fuse Breaking (ISFB) 215 A (15 ms) Magnetic circuit breaker tripping A1…A40 / B2…B25 / C1…C13 / Z1 …Z16 Derating > 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) 32 V DC
Control deviation < 0.5 % (Static load change 10 % … 90 %)
< 3 % (Dynamic load change 10 % … 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 960 W
1080 W
1440 W
Maximum no-load power dissipation < 5 W (400 V AC)
< 5 W (480 V AC)
Power loss nominal load max. < 45 W (400 V AC)
< 45 W (480 V AC)
Power dissipation SLEEP MODE < 2 W (400 V AC)
< 2 W (480 V AC)
Crest factor type. 1.6 (400 V AC)
type. 1.9 (480 V AC)
Rise time < 1 s (UOut = 10 % … 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes