AC operation
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current typ. 15 A (at 25 °C)
Inrush current integral (I2t) < 0.6 A2s
Inrush current limitation 15 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time typ. 55 ms (120 V AC)
typ. 56 ms (230 V AC)
Current consumption 2.4 A (100 V AC)
1.9 A (120 V AC)
1.1 A (230 V AC)
1.1 A (240 V AC)
Nominal power consumption 221 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time < 1 s
Typical response time 300 ms (from SLEEP MODE)
Input fuse 8 A (slow-blow, internal)
Recommended breaker for input protection 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE < 3.5 mA
0.7 mA (264 V AC, 60 Hz)
Efficiency typ. 91.2 % (120 V AC)
typ. 92 % (230 V AC)
Nominal output voltage 12 V DC
Setting range of the output voltage (USet) 12 V DC ... 15 V DC (constant capacity)
Nominal output current (IN) 15 A
Static Boost (IStat.Boost) 17.5 A
Dynamic Boost (IDyn.Boost) 20 A (5 s)
Selective Fuse Breaking (ISFB) 60 A (15 ms)
Magnetic circuit breaker tripping A1...A6 / B2...B6 / C1...C2 / Z1...Z6
Derating > 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 25 V DC
Protection against overvoltage at the output (OVP) ≤ 18 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 70 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 180 W
210 W
240 W
Apparent power 660 VA ()
644 VA ()
Maximum no-load power dissipation < 4 W (120 V AC)
< 4 W (230 V AC)
Power loss nominal load max. < 18 W (120 V AC)
< 16 W (230 V AC)
Power dissipation SLEEP MODE < 4 W (120 V AC)
< 4 W (230 V AC)
Crest factor typ. 1,58 (120 V AC)
typ. 1,59 (230 V AC)
Rise time < 1 s (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Signal
Signal ground SGnd Reference potential for Out1, Out2, and Rem
Signal Out 1 (configurable)
Digital 24 V DC 20 mA
Default 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet