Maximum power dissipation for nominal condition | 0.22 W |
Test voltage (Winding/contact) | 4 kV AC (50 Hz, 1 min., winding/contact) |
Insulation characteristics: Coil/contact | |
Rated insulation voltage | 250 V |
Rated impulse withstand voltage | 6 kV |
Overvoltage category | III |
Degree of pollution | 3 |
Input
Coil side | |
Nominal input voltage UN | 24 V DC |
Input voltage range | 18.5 V DC … 33.6 V DC (20 °C) |
Drive and function | monostable |
Drive (polarity) | polarized |
Typical input current at UN | 9 mA |
Typical response time | 5 ms |
Typical release time | 8 ms |
Protective circuit | Reverse polarity protection; Polarity protection diode |
Surge protection; Freewheeling diode | |
Operating voltage display | Yellow LED |
Out put
Switching | |
Contact switching type | 1 changeover contact |
Type of switch contact | Single contact |
Contact connection type | Power contact |
Contact material | AgSnO |
Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC… or …FBST 500…) |
Minimum switching voltage | 5 V (100 mA) |
Limiting continuous current | 6 A |
Maximum inrush current | 10 A (4 s) |
Min. switching current | 10 mA (12 V) |
Short-circuit current | 200 A (conditional short-circuit current) |
Interrupting rating (ohmic load) max. | 140 W (at 24 V DC) |
20 W (at 48 V DC) | |
18 W (at 60 V DC) | |
23 W (at 110 V DC) | |
40 W (at 220 V DC) | |
1500 VA (for 250 V AC) | |
Output fuse | 4 A gL/gG NEOZED |
Switching capacity | 2 A (at 24 V, DC13) |
0.2 A (at 110 V, DC13) | |
0.1 A (at 220 V, DC13) | |
3 A (at 24 V, AC15) | |
3 A (at 120 V, AC15) | |
3 A (at 230 V, AC15) |