RELAY MODULE KCD0-RSH-1.1D.1 – PEPPERL+FUCHS
- Technical information
- Download catalog
1-channel signal conditioner 24 V DC supply (loop powered) Logic input 19 V DC … 26.5 V DC, non-polarized Relay contact output for de-energized to safe function Test pulse immunity Up to SIL 3 acc. to IEC/EN 61508 Up to PL e acc. to EN/ISO 13849 Input Connection side control side Connection Input terminals 5, 6 ; test input terminals 7, 8, 9, 10 Pulse/Pause ratio 150 ms / 150 ms Test pulse length max. 4 ms from DO card Test input see functional safety manual Signal level 0-signal: -5 … 5 V 1-signal: 19 … 26.5 V Rated current 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) Output Connection side field side Connection terminals 1, 2 Contact loading 253 V AC/3 A/cos φ 0.7; 30 V DC/3 A resistive load 253 V AC / 1/8 HP Minimum switch current 10 mA / 24 V DC Energized/De-energized delay 150 ms / 150 ms Mechanical life 5 x 106 switching cycles