2904600 – QUINT4-PS/1AC/24DC/5 – BỘ NGUỒN QUINT 1 PHA 5A – PHOENIX CONTACT – TIENHUNGTECH
- 技术信息
- 下载目录
- 照片逼真
AC operation
Network type Star network
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
Derating < 100 V AC (1 %/V)
Electric strength, max. 300 V AC 60 s
Typical national grid voltage 120 V AC
230 V AC
Voltage type of supply voltage AC
Inrush current typ. 14 A (at 25 °C)
Inrush current integral (I2t) < 0.3 A2s
Inrush current limitation 14 A (after 1 ms)
AC frequency range 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN) 50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time typ. 28 ms (120 V AC)
typ. 38 ms (230 V AC)
Current consumption 1.7 A (100 V AC)
1.5 A (120 V AC)
0.9 A (230 V AC)
0.8 A (240 V AC)
Nominal power consumption 163 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.82
Switch-on time < 500 ms
Typical response time 300 ms (from SLEEP MODE)
Input fuse 6.3 A (slow-blow, internal)
Recommended breaker for input protection 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE < 3.5 mA
1.1 mA (264 V AC, 60 Hz)
Efficiency typ. 88.8 % (120 V AC)
typ. 89.2 % (230 V AC)
Output characteristic U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage 24 V DC
Setting range of the output voltage (USet) 24 V DC ... 29.5 V DC (constant capacity)
Nominal output current (IN) 5 A
Static Boost (IStat.Boost) 6.25 A
Dynamic Boost (IDyn.Boost) 10 A (5 s)
Selective Fuse Breaking (ISFB) 30 A (15 ms)
Magnetic circuit breaker tripping A1 ... A4 / B2 / C1 ... C2 / Z1 ... Z4
Derating > 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Control deviation < 0.5 % (Static load change 10 % ... 90 %)
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 30 mVPP (with nominal values)
Short-circuit-proof yes
No-load proof yes
Output power 120 W
150 W
240 W
Apparent power 180 VA (120 V, UOUT = 24 V, IOUT = stat. Boost)
198 VA (230 V, UOUT = 24 V, IOUT = stat. Boost)
Maximum no-load power dissipation < 3 W (120 V AC)
< 3 W (230 V AC)
Power loss nominal load max. < 17 W (120 V AC)
< 16 W (230 V AC)
Power dissipation SLEEP MODE < 3 W (120 V AC)
< 3 W (230 V AC)
Crest factor typ. 1.55 (120 V AC)
typ. 1.78 (230 V AC)
Rise time 50 ms (UOut = 10 % ... 90 %)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes