2866459 – TRIO-PS/3AC/24DC/10 – BỘ NGUỒN TRIO 3 PHA 10A – PHOENIX CONTACT – TIENHUNGTECH
- 技术信息
- 下载目录
- 照片逼真
AC operation
Nominal input voltage range 2x / 3x 400 V AC … 500 V AC
Input voltage range 3x 320 V AC … 575 V AC
2x 360 V AC … 575 V AC (for 2-phase operation)
Input voltage range AC 3x 320 V AC … 575 V AC
2x 360 V AC … 575 V AC (for 2-phase operation)
Voltage type of supply voltage AC
Inrush current < 15 A
Inrush current integral (I2t) 0.2 A2s
AC frequency range 45 Hz ... 65 Hz
Mains buffering time > 20 ms (3x 400 V AC)
Current consumption 3x 0.6 A (400 V AC)
3x 0.5 A (480 V AC)
Nominal power consumption 456 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.59
Typical response time < 1 s
Strike voltage of gas-filled surge arrester (input to PE) <
Input fuse <
Permissible backup fuse B6 B10 B16
Permissible DC backup fuse <
Recommended breaker for input protection < 6 A ... 16 A (Characteristics B, C, D, K)
Recommended fuse for input protection <
Discharge current to PE < 3.5 mA
Efficiency 88.5 % (at 400 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (UOUT = 24 V DC)
Derating 55 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation approx. 15 A
Control deviation < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 10 mVPP
Output power 240 W
Peak switching voltages nominal load < 30 mVPP
Maximum no-load power dissipation 7.5 W
Power loss nominal load max. 34 W
Rise time < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes